What Creates Coil Freeze Events? 
(and the Revolutionary Sentry Guard Design)

There are numerous reasons why water and steam coils can have major freeze events. The damage is often extensive enough to require a coil replacement. The following reviews some of the major freeze event causes.

  • Coils not drained properly when winterized - This problem may be out of your control. Many chilled water coil circuits and placement of drains makes it impossible to fully drain the coil. Also some manufacturers design uphill coil circuitry that prevent full drainage.
  • Steam coil selection and the system design prevent condensate from being removed - These problems include lack of installed vacuum breakers, improper sizing and location of traps and inadequate coil tube sizes and pitch. A steam coil in operation can have a freeze event if the condensate removal is inadequate.
  • Air stratification across the face of the coil - Air stratification can occur when preheat coils are located very close to an outside air damper or louver. High wind, along with just a minor mechanical breakdown, can create a rapid freeze event.
  • Mechanical Breakdown(s) - Breakdowns can be as simple as a valve malfunction, an inoperable pump, and/or a variety of freeze stat problems. Any or all of these can create a freeze event in a matter of minutes. 


Freeze damage occurs when liquid inside the coils (heat exchanger) reduces its temperature and the liquid begins to turn into a solid (ice). Most people believe this expansion of ice is what ultimately creates the damage. However, it is actually the increase in pressure inside the coil that creates the damage. Pressure builds inside the coil until it can no longer be contained by the coil construction. A textbook freeze failure will always have bloating of the weakened area with a crack forming in the middle of the bloat.

Why is the damage often located at the back end of a return bend? Many times this is the weakest area of the coil, and the rising pressure seeks and finds this weak area.

Why is the damage sometimes located on the tubes and not on the return bend? The pressure builds but so does the ice. Sometimes the ice can form in the tubes and cut off the pressure to the outside of the coil (return bend). This causes the tube to fail before the return bend fails.

 


USA Coil & Air has developed a patented coil series known as Sentry Guard™. We can't prevent the actual freeze event, but we can prevent the damage to the coil from that event.


How is damage prevented by the Sentry Guard™ Coil design? The Sentry Guard™ revolutionary freeze-relief plugs located on all the return bends and headers at both ends of the coil absorb the increased pressure and fail before the tubes and return bends. These screw-on/screw-off type plugs can be replaced easily and the coil(s) becomes operable immediately. These plugs can release the pressure at or about 650 PSI. Our research has shown that damage to a tube or bend must exceed 1,000 PSI. The early release of pressure at 650 PSI gives you protection from any damage due to a freeze event.


We've recently heard of a design that we believe won't work for many reasons. Those reasons include lack of coverage at both ends of the coil, the rearrangement of circuits that may reduce performance of the coil, and devices that occupy too much space - thereby reducing the face area and performance even further.

Many fresh air systems are prone to a freeze event, and the down time and replacement is counterproductive and very costly. Examples are: hospitals, schools, universities, public areas and specialized industrial processes. All of these have large percentages of air delivered from the outside.

USA Coil & Air has been building the Sentry Guard™ for over 18 years. Our knowledge and experience provides you with a product that works and we guarantee it!

Learn More →

Fan Coil Units
Extensive line of horizontal & vertical units from 200 to 2,000 CFM. Can ship with valves and controls
Read More →
Belt Drive Air Handler
Belt Drive Air Handlers
11 Horizontal & 11 Vertical single wall units for applications requiring 800-12,000 CFM
Read More →
"U" Tube Bundle
Tube Bundles
Offering a wide variety of materials, including: carbon steel, stainless steel, cupro-nickel and admiralty brass
Read More →
Central Station Air Handler
Central Station AHUs
Double-wall units built to match existing unit sizes, ship in sections for easy access through doorways, elevators, stairwells and into mechanical rooms
Read More →
Recent Articles
   
January 2016
Got the Condenser Coil Blues?
Although there are a myriad of reasons why A/C and refrigeration systems have problems - many of them can be traced back to the "condenser coil".
Learn More →


September 2015
When to Re-tube?
One problem a lot of people seem to have when dealing with heat exchangers and tube bundles is the terminology used by our industry when describing the various parts of the exchanger...
Learn More →
July 2015
Computer Coil Selections - How They Really Happen!
This one is for all you closet engineers out there who actually want to know how coils are selected and the factors that go into picking a coil.
Learn More →
June 2015
Helpful Hints for Coil Replacement
10 Things you need to know in order to replace coils adequately including helpful hints to make your job easier.
Learn More →
USA Coil & Air

USA Coil & Air is one of the largest and oldest replacement coil companies in our industry. Over the years, we have developed other great lines of HVAC equipment to include direct drive and belt drive fan coil units, central station units with emphasis on the replacement market as well as replacement chillers, water cooled condensers and tube bundles.

 

Every one of our lines is specific to the quick shipment and requirements of the replacement market. You will find that we make this process simple and easy.  We have stocking and expedited schedules for all of our equipment and know how to deal with existing facilities and the problems related to shipment and delivery. We also pride ourselves with great application engineering so that you don't replace equipment without having a true understanding of why the original might have failed and what can be provided in replacement to increase longevity.

 

Many of you may already be USA Coil & Air customers and we thank you for your current and past business. If you are not a customer yet, we hope you will be in the very near future. We believe this newsletter will give you keen insight into our equipment, typical applications and will answer service questions as well. We hope you enjoy.

 


11 General Warren Blvd., Malvern, PA 19355, USA

(800) 872-2645